Table 12- 34 Overview of power loss at rated operation for power units with internal air cooling
Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Smart Line Modules Booksize
5 kW
10 kW
16 kW
36 kW
55 kW
Smart Line Modules Booksize Compact
16 kW
Basic Line Modules
20 kW
40 kW
100 kW
Single Motor Modules Booksize
3 A
5 A
9 A
18 A
30 A
45 A
60 A
85 A
132 A
200 A
Single Motor Modules Booksize Compact
3 A
5 A
9 A
18 A
784
(including electronics losses)
Unit
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Power loss
282.8
666
945.6
1383.6
2243.2
79.2
141.6
187.8
406
665.6
187.8
144
283.6
628
50.4
73.4
100.4
185,4
309.2
455.2
615.2
786
1270.4
2070.4
68
1)
98
1)
100.4
185.4