12.11.3
Cold plate with an external liquid heat sink
12.11.3.1
Configuration and conditions
When an external liquid heat sink is used, the power sections are all installed on a plate
through which cooling water flows to cool the power units. The size of the liquid heat sink
can be adjusted in line with the size of the drive line-up.
General conditions to be observed
1. The maximum temperature within the cabinet is 40 °C
2. The maximum permissible heat-sink temperature is module-dependent. Refer to the
3. The customer must take measures to protect the devices against condensation (see Anti-
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
(inlet air temperature of the power sections). The maximum temperature inside the
cabinet for derating is 55 °C. For the relevant specifications, refer to the "Technical data".
"Technical data" for more information. A temperature sensor in the power unit measures
the temperature and can be read via parameter (see SINAMICS S120/S150 List Manual).
condensation measures (Page 807))
Cabinet design and EMC Booksize
12.11 Information on cold plate cooling
769