Parameter Description
P0821

BI: DDS bit 1

CStat:
CT
P-Group: COMMANDS
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter
P0820).
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Note:
P0820 is also relevant for drive data set (DDS) selection.
3.14

BICO command parameters

P0840[3]

BI: ON/OFF1

CStat:
CT
P-Group: COMMANDS
Allows ON/OFF1 command source to be selected using BICO.
The first three digits describe the parameter number of the command source; the last digit denotes the bit
setting for that parameter. The default setting (ON right) is digital input 1 (722.0). Alternative source possible
only when function of digital input 1 is changed (via P0701) before changing value of P0840.
f
f max
(P1082)
f
2
P2167
0
r0052 Bit02
Operation
Pulse
cancellation
Index:
P0840[0] : 1st. Command data set (CDS)
P0840[1] : 2nd. Command data set (CDS)
P0840[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0
= ON/OFF1 via BOP
Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).
Note:
-
OFF1 means a ramp stop down to 0 using P1121.
-
OFF1 is low active.
-
For the priority of all soft commands, the following applies: OFF2, OFF3, OFF1
102
Datatype: U32
Active: first confirm
Datatype: U32
Active: first confirm
ON
P1120
Min:
Unit: -
Def:
QuickComm.: No
Max:
Min:
Unit: -
Def:
QuickComm.: No
Max:
OFF1
t
P2168
t
P2168
t
t
down,OFF1
down
,
P1121
t
MICROMASTER 440
Issue 01/06
Level
0:0
3
0:0
4095:0
Level
0:0
3
722:0
4000:0
f
act ,motor
f
act ,inverter
f
2
=
P1121
OFF
1
P1082
Parameter List