Parameter Changeable Via; Co: Last Fault Code - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Parameter Description
P0927

Parameter changeable via

CStat:
CUT
P-Group: COMM
Specifies the interfaces which can be used to change parameters.
This parameter allows the user to easily protect the inverter from unauthorized modification of parameters.
Annotation: Parameter P0927 is not password protected.
Bitfields:
Bit00
PROFIBUS / CB
Bit01
BOP
Bit02
USS on BOP link
Bit03
USS on COM link
Example:
Bits 0, 1, 2 and 3 set:
The default setting allows parameters to be changed via any interface. If all bits are set, the parameter is
displayed on BOP as follows:
BOP:
P0927
Bits 0, 1, 2 and 3 reset:
This setting allows no parameters to be modified via any interface with the exception of P0003 and P0927. If
all bits are reset, the parameter is displayed on BOP as follows:
BOP:
P0927
Details:
The seven-segment display is explained in the "Introduction to MICROMASTER System Parameters" in this
handbook.
r0947[8]

CO: Last fault code

P-Group: ALARMS
Displays fault history according to the diagram below
where:
-
"F1" is the first active fault (not yet acknowledged).
-
"F2" is the second active fault (not yet acknowledged).
-
"F1e" is the occurrence of the fault acknowledgement for F1 & F2.
This moves the value in the 2 indices down to the next pair of indices, where they are stored. Indices 0 & 1
contain the active faults. When faults are acknowledged, indices 0 & 1 are reset to 0.
r0947[0]
F1
r0947[1]
r0947[2]
r0947[3]
r0947[4]
r0947[5]
r0947[6]
r0947[7]
Index:
r0947[0] : Recent fault trip --, fault 1
r0947[1] : Recent fault trip --, fault 2
r0947[2] : Recent fault trip -1, fault 3
r0947[3] : Recent fault trip -1, fault 4
r0947[4] : Recent fault trip -2, fault 5
r0947[5] : Recent fault trip -2, fault 6
r0947[6] : Recent fault trip -3, fault 7
r0947[7] : Recent fault trip -3, fault 8
Example:
If the inverter trips on undervoltage and then receives an external trip before the undervoltage is
acknowledged, you will obtain:
-
r0947[0] = 3
-
r0947[1] = 85 External trip (F0085)
Whenever a fault in index 0 is acknowledged (F1e), the fault history shifts as indicated in the diagram
above.
Dependency:
Index 1 used only if second fault occurs before first fault is acknowledged.
Details:
See "Faults and Warnings"
106
Datatype: U16
Active: first confirm
Datatype: U16
F2
F1e
F1e
F1e
F1e
F1e
F1e
Undervoltage (F0003)
Min:
Unit: -
Def:
QuickComm.: No
Max:
0
NO
0
NO
0
NO
0
NO
Min:
Unit: -
Def:
Max:
Active
Fault Codes
Most recent
Fault Codes - 1
Most recent
Fault Codes - 2
Most recent
Fault Codes - 3
MICROMASTER 440
Issue 01/06
Level
0
2
15
15
1
YES
1
YES
1
YES
1
YES
Level
-
2
-
-
Parameter List
6SE6400-5BB00-0BP0