Speed encoder

P0400[3]

Select encoder type

CStat:
CT
P-Group: ENCODER
Selects encoder type (number of encoder channels).
Possible Settings:
0
Disabled
1
Single channel encoder
2
Quadrature encoder without zero pulse
Index:
P0400[0] : 1st. Drive data set (DDS)
P0400[1] : 2nd. Drive data set (DDS)
P0400[2] : 3rd. Drive data set (DDS)
Dependency:
Following table displays the setting of P0400 which depends upon the number of encoder channels:
Parameter
P0400 = 1
P0400 = 2
Following table displays the setting the of the encoder DIPs on the encoder option modul which have to be
set depending on the encoder type (TTL, HTL) and encoder output:
Type
TTL
(e.g.
1XP8001-2)
HTL
(e.g.
1XP8001-1)
Caution:
When using Vector Control with encoder-feedback , the direction of rotation of the Encoder and Motor must
be the same. If this is not achieved, then the functional operation of the Vector Control will not be
guaranteed (positive instead of negative feedback). Extreme care must therefore be taken with respect to
the connection of the motor to the inverter as well as the correct connection of the encoder to the Encoder
module. Motor and Encoder must not be incorrectly wired up !
When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f
mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in
-
sign and
-
magnitude (with a deviation of only a few percent).
Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23).
P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions
is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating
Instructions of the encoder module for more information.
Note:
Encoders with zero pulse can also be connected, but the zero pulse is not used in MM4.
The term "quadrature" in setting 2 refers to two periodic functions separated by a quarter cycle or 90
degrees.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: Immediately
Terminal
Track
A
A
AN
A
B
A
AN
B
BN
Output
differential
single ended
111111
010101
101010
000000
Parameter Description
Min:
0
Unit: -
Def:
0
QuickComm.: No
Max:
2
Encoder output
single ended
differential
single ended
differential
Level
2
67