Ramp-Down Final Rounding Time; Rounding Type - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Parameter Description
P1133[3]

Ramp-down final rounding time

CStat:
CUT
P-Group: SETPOINT
Defines rounding time at end of ramp-down as shown in P1130 (ramp-up initial rounding time).
Index:
P1133[0] : 1st. Drive data set (DDS)
P1133[1] : 2nd. Drive data set (DDS)
P1133[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1130.
P1134[3]

Rounding type

CStat:
CUT
P-Group: SETPOINT
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g.
new setpoint, OFF1, OFF3, REV).
This smoothing is applied, if the motor is ramped-up or ramped-down and
-
P1134 = 0,
-
P1132 > 0, P1133 > 0 and
-
the setpoint is not yet reached.
P1132 > 0, P1133 > 0
f
f
Set
P1134 = 0
f
f
Set
P1134 = 1
ON
OFF1
Possible Settings:
0
Continuous smoothing
1
Discontinuous smoothing
Index:
P1134[0] : 1st. Drive data set (DDS)
P1134[1] : 2nd. Drive data set (DDS)
P1134[2] : 3rd. Drive data set (DDS)
Dependency:
No effect until P1132 (Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.
134
Datatype: Float
Active: first confirm
Datatype: U16
Active: Immediately
Setpoint reached
P1132
P1133
Setpoint reached
P1132
P1133
Min:
0.00
Unit: s
Def:
0.00
QuickComm.: No
Max:
40.00
Min:
0
Unit: -
Def:
0
QuickComm.: No
Max:
1
Setpoint not reached
P1132
P1133
Setpoint not reached
P1133
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
2
Level
2
t
t
t
Parameter List

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents