Debounce Time For Digital Inputs; Pnp / Npn Digital Inputs - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P0724

Debounce time for digital inputs

CStat:
CT
P-Group: COMMANDS
Defines debounce time (filtering time) used for digital inputs.
Possible Settings:
0
No debounce time
1
2.5 ms debounce time
2
8.2 ms debounce time
3
12.3 ms debounce time
P0725

PNP / NPN digital inputs

CStat:
CT
P-Group: COMMANDS
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously.
The following is valid by using the internal supply:
Possible Settings:
0
NPN mode ==> low active
1
PNP mode ==> high active
Value:
NPN: Terminals 5/6/7/8/16/17 must be connected via terminal 28 ( O V).
PNP: Terminals 5/6/7/8/16/17 must be connected via terminal 9 (24 V).
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: Immediately
QuickComm.: No
Datatype: U16
Unit: -
Active: Immediately
QuickComm.: No
Parameter Description
Level
Min:
0
3
Def:
3
Max:
3
Level
Min:
0
3
Def:
1
Max:
1
83