Parameter Description
3.18

Motorized potentiometer (MOP)

P1031[3]

Setpoint memory of the MOP

CStat:
CUT
P-Group: SETPOINT
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.
Possible Settings:
0
MOP setpoint will not be stored
1
MOP setpoint will be stored (P1040 is updated)
Index:
P1031[0] : 1st. Drive data set (DDS)
P1031[1] : 2nd. Drive data set (DDS)
P1031[2] : 3rd. Drive data set (DDS)
Note:
On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint
of the MOP).
P1032

Inhibit negative MOP setpoints

CStat:
CT
P-Group: SETPOINT
This parameter suppresses negative setpoints of the MOP output r1050.
Possible Settings:
0
Neg. MOP setpoint is allowed
1
Neg. MOP setpoint inhibited
Note:
The reversing functions (e.g. BOP-Reverse button if P0700 = 1) are not affected by the settings of P1032.
Use P1110 to fully prevent change of direction in setpoint channel.
P1035[3]

BI: Enable MOP (UP-command)

CStat:
CT
P-Group: COMMANDS
Defines source for motor potentiometer setpoint increase frequency.
Index:
P1035[0] : 1st. Command data set (CDS)
P1035[1] : 2nd. Command data set (CDS)
P1035[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.D
= MOP up via BOP
P1036[3]
BI: Enable MOP (DOWN-command)
CStat:
CT
P-Group: COMMANDS
Defines source for motor potentiometer setpoint decrease frequency.
Index:
P1036[0] : 1st. Command data set (CDS)
P1036[1] : 2nd. Command data set (CDS)
P1036[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E
= MOP down via BOP
120
Datatype: U16
Unit: -
Active: Immediately
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Issue 01/06
Min:
0
Def:
0
Max:
1
Min:
0
Def:
1
Max:
1
Min:
0:0
Def:
19:13
Max:
4000:0
Min:
0:0
Def:
19:14
Max:
4000:0
MICROMASTER 440
Parameter List