3.29.2.4

Torque control

P1500[3]

Selection of torque setpoint

CStat:
CT
P-Group: CONTROL
Selects torque setpoint source. In the table of possible settings below, the main setpoint is selected from the
least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0 through
to x7).
Possible Settings:
0
No main setpoint
2
Analog setpoint
4
USS on BOP link
5
USS on COM link
6
CB on COM link
7
Analog setpoint 2
20
No main setpoint
22
Analog setpoint
24
USS on BOP link
25
USS on COM link + Analog setpoint
26
CB on COM link
27
Analog setpoint 2 + Analog setpoint
40
No main setpoint
42
Analog setpoint
44
USS on BOP link
45
USS on COM link + USS on BOP link
46
CB on COM link
47
Analog setpoint 2 + USS on BOP link
50
No main setpoint
52
Analog setpoint
54
USS on BOP link
55
USS on COM link + USS on COM link
57
Analog setpoint 2 + USS on COM link
60
No main setpoint
62
Analog setpoint
64
USS on BOP link
66
CB on COM link
67
Analog setpoint 2 + CB on COM link
70
No main setpoint
72
Analog setpoint
74
USS on BOP link
75
USS on COM link + Analog setpoint 2
76
CB on COM link
77
Analog setpoint 2 + Analog setpoint 2
Index:
P1500[0] : 1st. Command data set (CDS)
P1500[1] : 2nd. Command data set (CDS)
P1500[2] : 3rd. Command data set (CDS)
Example:
Setting 24 selects the main setpoint (4) derived from the USS on BOP link with the additional setpoint (2)
derived from the analog input. Single digits are main setpoints only with no additional setpoint.
Example P1500 = 24 :
2
4 ⇒ P1503 = 755.0
P1500 =
4
P1500 = 2
ADC
USS
BOP link
USS
COM link
CB
COM link
ADC2
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: first confirm
+ Analog setpoint
+ Analog setpoint
+ Analog setpoint
+ Analog setpoint
+ USS on BOP link
+ USS on BOP link
+ USS on BOP link
+ USS on BOP link
+ USS on COM link
+ USS on COM link
+ USS on COM link
+ CB on COM link
+ CB on COM link
+ CB on COM link
+ CB on COM link
+ Analog setpoint 2
+ Analog setpoint 2
+ Analog setpoint 2
+ Analog setpoint 2
P1503
r0755
P1511
⇒ P1511 = r2015.1
r2015
2
P1000 =
4
Additonal
torque setpoint
4
P1000 = 2
Unit: -
QuickComm.: Yes
CI: Torque setpoint
CO: Act. ADC after scal. [4000h]
CI: Additional torque setpoint
CO: PZD from BOP link (USS)
Sequence
control
Torque
control
Torque
setpoint
Parameter Description
Level
Min:
0
2
Def:
0
Max:
77
173