Parameter Description
P2802[14] Activate FFBs
CStat:
CUT
P-Group: TECH
Free function blocks (FFB) are enabled in two steps.
1. Parameter P2800 enables all free function blocks , normally (P2800 = 1)
2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0
oder P2802[x] > 0)
In addition, Parameters P2801 and P2802 determine the chronological order of each function block. The
following table shows that the priority increases from left to right and from bottom to top.
Level
3
Level
2
Level
1
0
Inactive
Possible Settings:
0
Not Active
1
Level 1
2
Level 2
3
Level 3
Index:
P2802[0] : Enable timer 1
P2802[1] : Enable timer 2
P2802[2] : Enable timer 3
P2802[3] : Enable timer 4
P2802[4] : Enable ADD 1
P2802[5] : Enable ADD 2
P2802[6] : Enable SUB 1
P2802[7] : Enable SUB 2
P2802[8] : Enable MUL 1
P2802[9] : Enable MUL 2
P2802[10] : Enable DIV 1
P2802[11] : Enable DIV 2
P2802[12] : Enable CMP 1
P2802[13] : Enable CMP 2
Example:
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2
FFBs will be calculated in following order:
P2802[3], P2801[3] , P2801[4], P2802[4]
Dependency:
-
Set P2800 to 1 to enable function blocks.
-
All active function blocks will be calculated in every 132 ms.
242
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Issue 01/06
Min:
0
Def:
0
Max:
3
Priority 2
low
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0