Issue 01/06
P0010

Commissioning parameter

CStat:
CT
P-Group: ALWAYS
Filters parameters so that only those related to a particular functional group are selected.
Possible Settings:
0
Ready
1
Quick commissioning
2
Inverter
29
Download
30
Factory setting
Dependency:
-
Reset to 0 for inverter to run.
-
P0003 (user access level) also determines access to parameters.
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important
parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after
the other. The end of quick commissioning and the start of internal calculation will be done by setting P3900
= 1 - 3. Afterward parameter P0010 and P3900 will be reset to zero automatically.
P0010 = 2
For service purposes only.
P0010 = 29
To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set to 29 by
the PC tool. When download has been finished PC tool resets parameter P0010 to zero.
P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will be
started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters to their
default settings. This can prove beneficial if you experience problems during parameter setup and wish to
start again. Duration of factory setting will take about 60 s.
P0011

Lock for user defined parameter

CStat:
CUT
P-Group: FUNC
Details:
See parameter P0013 (user defined parameter)
P0012

Key for user defined parameter

CStat:
CUT
P-Group: FUNC
Details:
See parameter P0013 (user defined parameter).
P0013[20] User defined parameter
CStat:
CUT
P-Group: FUNC
Defines a limited set of parameters to which the end user will have access.
Instructions for use:
1. Set P0003 = 3 (expert user)
2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The
following values are fixed and cannot be changed:
-
P0013 index 19 = 12 (key for user defined parameter)
-
P0013 index 18 = 10 (commissioning parameter filter)
-
P0013 index 17 = 3 (user access level)
4. Set P0003 = 0 to activate the user defined parameter.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
0
1
Def:
0
Max:
30
Level
Min:
0
3
Def:
0
Max:
65535
Level
Min:
0
3
Def:
0
Max:
65535
Level
Min:
0
3
Def:
0
Max:
65535