Digital Inputs; Function Of Digital Input 1 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
3.9

Digital inputs

P0701[3]

Function of digital input 1

CStat:
CT
P-Group: COMMANDS
Selects function of digital input 1.
DIN channel (e.g. DIN1 - PNP (P0725 = 1))
Kl.9
P24 (PNP)
Kl.28
0 V (NPN)
Possible Settings:
0
Digital input disabled
1
ON/OFF1
2
ON reverse /OFF1
3
OFF2
- coast to standstill
4
OFF3
- quick ramp-down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
15
Fixed setpoint (Direct selection)
16
Fixed setpoint (Direct selection + ON)
17
Fixed setpoint (Binary coded selection + ON)
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
Index:
P0701[0] : 1st. Command data set (CDS)
P0701[1] : 2nd. Command data set (CDS)
P0701[2] : 3rd. Command data set (CDS)
Dependency:
Setting 99 (enable BICO parameterization) requires
-
P0700 command source or
-
P0010 = 1, P3900 = 1, 2 or 3 quick commissioning or
-
P0010 = 30, P0970 = 1 factory reset in order to reset.
Notice:
Setting 99 (BICO) for expert use only.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: first confirm
PNP/NPN DIN
0 ... 1
P0725 (1)
Debounce time : DIN
24
V
0
0
24 V
1
1
0 V
Min:
Unit: -
Def:
QuickComm.: No
Max:
0 ... 3
P0724 (3)
T
0
&
r0722
r0722
.0
CO/BO: Bin.inp.val
Parameter Description
Level
0
2
1
99
P0701
Function
Pxxxx BI : ...
77

Hide quick links:

Advertisement

Table of Contents
loading