Setpoint Channel; Ci: Main Setpoint; Ci: Main Setpoint Scaling; Bi: Disable Additional Setpoint - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
3.20

Setpoint channel

P1070[3]

CI: Main setpoint

CStat:
CT
P-Group: SETPOINT
Defines source of main setpoint.
Index:
P1070[0] : 1st. Command data set (CDS)
P1070[1] : 2nd. Command data set (CDS)
P1070[2] : 3rd. Command data set (CDS)
Common Settings:
755
= Analog input 1 setpoint
1024
= Fixed frequency setpoint
1050
= Motor potentiometer (MOP) setpoint
P1071[3]

CI: Main setpoint scaling

CStat:
CT
P-Group: SETPOINT
Defines source of the main setpoint scaling.
Index:
P1071[0] : 1st. Command data set (CDS)
P1071[1] : 2nd. Command data set (CDS)
P1071[2] : 3rd. Command data set (CDS)
Common Settings:
755
= Analog input 1 setpoint
1024
= Fixed frequency setpoint
1050
= Motor potentiometer (MOP) setpoint
P1074[3]

BI: Disable additional setpoint

CStat:
CUT
P-Group: COMMANDS
Disables additional setpoint
Index:
P1074[0] : 1st. Command data set (CDS)
P1074[1] : 2nd. Command data set (CDS)
P1074[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99))
P1075[3]
CI: Additional setpoint
CStat:
CT
P-Group: SETPOINT
Defines source of the additional setpoint (to be added to main setpoint).
Index:
P1075[0] : 1st. Command data set (CDS)
P1075[1] : 2nd. Command data set (CDS)
P1075[2] : 3rd. Command data set (CDS)
Common Settings:
755
= Analog input 1 setpoint
1024
= Fixed frequency setpoint
1050
= Motor potentiometer (MOP) setpoint
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
0:0
3
Def:
755:0
Max:
4000:0
Level
Min:
0:0
3
Def:
1:0
Max:
4000:0
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
125