Issue 01/06
3.34

Communication parameters (USS, CB)

P2009[2]

USS denormalization

CStat:
CT
P-Group: COMM
Enables denormalization for USS.
Possible Settings:
0
Disabled
1
Enabled
Index:
P2009[0] : Serial interface COM link
P2009[1] : Serial interface BOP link
Note:
If denormalization is enabled, the main setpoint (word 2 in PZD) is not interpreted as 100 % = 4000H, but as
"absolute" instead (e.g. 4000H = 16384 means 163.84 Hz ) if this is a frequency. Denormalization (P2009 =
1) only works for frequencies and is intended for backwards compatibility with MM3.
P2010[2]

USS baudrate

CStat:
CUT
P-Group: COMM
Sets baud rate for USS communication.
Possible Settings:
4
2400 baud
5
4800 baud
6
9600 baud
7
19200 baud
8
38400 baud
9
57600 baud
10
76800 baud
11
93750 baud
12
115200 baud
Index:
P2010[0] : Serial interface COM link
P2010[1] : Serial interface BOP link
P2011[2]

USS address

CStat:
CUT
P-Group: COMM
Sets unique address for inverter.
Index:
P2011[0] : Serial interface COM link
P2011[1] : Serial interface BOP link
Note:
You can connect up to a further 30 inverters via the serial link (i.e. 31 inverters in total) and control them
with the USS serial bus protocol.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
0
3
Def:
0
Max:
1
Level
Min:
4
2
Def:
6
Max:
12
Level
Min:
0
2
Def:
0
Max:
31