r2169

CO: Act. filtered frequency 3

P-Group: ALARMS
Filtered frequency for monitoring behind first-order lowpass filter.
-
|f_act| > f_1 (see P2155)
-
|f_act| > f_2 (see P2157)
-
|f_act| > f_3 (see P2159)
P2170[3]

Threshold current I_thresh

CStat:
CUT
P-Group: ALARMS
Defines threshold current in [%] relative to P0305 (rated motor current) to be used in comparisons of I_act
and I_Thresh as illustrated in the diagram below.
|I_act| > I_thresh
I_act
Index:
P2170[0] : 1st. Drive data set (DDS)
P2170[1] : 2nd. Drive data set (DDS)
P2170[2] : 3rd. Drive data set (DDS)
Note:
This threshold controls bit 3 in status word 3 (r0053).
P2171[3]

Delay time current

CStat:
CUT
P-Group: ALARMS
Defines delay time prior to activation of current comparison.
Index:
P2171[0] : 1st. Drive data set (DDS)
P2171[1] : 2nd. Drive data set (DDS)
P2171[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2170 (threshold current I_thresh)
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
Datatype: Float
Active: Immediately
1
0
Delay time current
0 ... 10000 [ms]
Threshold current
P2171.D ( 10)
0.0 ... 400.0 [%]
P2170.D (100.0)
Datatype: U16
Active: Immediately
Parameter Description
Min:
Unit: Hz
Def:
Max:
Min:
Unit: %
Def:
QuickComm.: No
Max:
| I_act | > I_thresh
0 T
r0053 Bit03
Min:
Unit: ms
Def:
QuickComm.: No
Max:
Level
-
2
-
-
Level
0.0
3
100.0
400.0
Level
0
3
10
10000
215