7.15.19 Fieldbus failure protection
This protection detacts if there is a communication
disturbance between the softstarter and the PLC.
If the softstarter is normally controlled over the fieldbus,
the fieldbus failure protection parameter specifies what will
happen.
This protection has a special action in addition to the
common types of operation:
Switch to I/O-control.
Fieldbus failure protection is configured with the
following parameters:
Parameter
19.03 Fieldbus failure out
19.04 Fieldbus failure op
7.15.20 Extension IO failure protection
This protection detacts if there is communication
disturbance between the softstarter and the Extension I/O
module.
7
Extension IO failure protection
is configured with the following parameters:
Parameter
19.05 Ext IO failure trip time
19.06 Ext IO failure out
19.07 Ext IO failure op
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Specifies the Event groups this
protection belongs to.
Sets the operation of this
protection.
Description
Sets the trip time for extension
IO failure protection.
Specifies the Event groups this
protection belongs to.
Sets the operation of this
protection.
Setting range
Default value
Eventgroup 0 ... 6
2
Off, Stop manual,
Off
Stop auto, Indication.
Setting range
Default value
300 ... 30000 ms

1000 ms

Eventgroup 0 ... 6
2
Off, Stop manual,
Off
Stop auto, Indication.