ABB PSTX30 Installation And Commissioning Manual page 117

Hide thumbs Also See for PSTX30:
Table of Contents

Advertisement

Parameter
Description
number
08
Sequence start
08.37
Kick start time seq 2
08.38
Torque limit lvl seq 2
08.39
Torque tune seq 2
08.40
Torque ctrl gain seq 2
08.60
Ie seq 3
08.61
Start mode seq 3
08.62
Start ramp time seq 3
08.63
Start ramp init lvl seq 3
08.64
Curr lim level seq 3
08.65
Kick start seq 3
08.66
Kick start level seq 3
08.67
Kick start time seq 3
08.68
Torque limit lvl seq 3
08.69
Torque tune seq 3
08.70
Torque ctrl gain seq 3
09
Automatic restart
09.01
Auto-reset delay time
09.02
Auto-restart
09.03
Auto-restart max attempts
10
Internal IO
10.01
In0 function
10.02
In1 function
10.03
In2 function
10.04
K4 function
10.05
K5 function
10.06
K6 function
10.07
AO reference
10.08
AO type
10.09
AO max value
10.10
AO min value
10.11
Ext therm sensor - ID
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting range
0.20 ... 2.00 s
20 ... 200 %
0 ... 1000 %
0.01 ... 10.00
9.0 ... 1250 A
Voltage ramp, Torque ramp, Full voltage start
1 ... 120 s
10 ... 99 %
0.5 ... 7.5 x I e
On / Off
50 ... 100 %
0.2 ... 2.00 s
20 ... 200 %
0 ... 1000 %
0.01 ... 10.0
0 ... 3600 s
On / Off
1 ... 10
None, Reset, Enable, Slow speed forward,
Slow speed reverse, Motor heating, Stand still
brake, Start reverse, User defined protection,
Emergency mode, Fieldbus disable control,
Start 1, Start 2, Start 3. *
0 ... 15 *
0 ... 15 *
None, Run, Top of ramp, Event group 0, Event
group 1, Event group 2, Event group 3, Event
group 4, Event group 5, Event group 6,
Sequence 1 RUN, Sequence 2 RUN,
Sequence 3 RUN, Sequence 1 TOR, Sequence
2 TOR, Sequence 3 TOR,
Run reverse **
0 ... 17 **
None, Run, Top of ramp, Event group 0,
Event group 1, Event group 2, Event group 3,
Event group 4, Event group 5, Event group 6,
Sequence 1 Run, Sequence 2 Run,
Sequence 3 Run
0-10 mA, 0-20 mA, 4-20 mA, 0-10 V
Motor current [A], Mains voltage [V], Active
power [kW], Active power [HP], Reactive power
[kVAr], Apparent power [kVA], Active energy
[kWh], Reactive energy [kVArh], COS [COS [Φ],
Motor temperature [%], Thyristor temperature
[%], Motor voltage [%]
Mains frequency [Hz], PT100 temperature
[centigrade], PTC resistance [Ω]
0.0 ... 1000000.0
0.0 ... 1000000.0
No sensor, PTC element, Three-wire PT100,
Two-wire PT100, Thermistor switch
Number of
Fieldbus
Default value
decimal
ID
2
0
0.20 s
0
0
150 %
0
0
100 %
2
0
0.02
1
0
9.0 A
0
0
Voltage ramp
0
0
10 s
0
0
30 %
1
0
7.0 x I e
0
0
Off
0
0
70 %
2
0
0.2 s
0
0
150 %
0
-
100 %
2
-
0.02
0
-
0 s
0
-
Off
0
-
5
0
130
Reset
0
131
None
0
132
None
0
133
Run
0
134
Top of ramp
0
135
Event group 0
0
137
4-20 mA
0
138
Motor current
[A]
0
139
500.0
0
140
0.0
0
-
No sensor
Actual
setting
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents