7.11 Automatic restart
The softstarter automatically restarts the motor after a
fault has occurred.
The primary requirement is that if a fault or protection has
been asserted, the softstarter shall automatically restart
the motor in order to ensure an uninterrupted process.
The event is reset only after the Auto-reset delay time
has transpired. If Auto-restart is enabled, an internal
start signal is given and the fault relay is not directly
activated. This is because the fault relay can sometimes
be connected to a breaker located upstream.
Until a successful start is carried out, several attempts to
restart are made with a fixed time interval between each.
During the time between each restart, the start digital
input signal is ignored.
If the fault still remain by the time a restart is made, this
will be seen as a failed restart attempt.
The fault relay will only be activated after the maximum
number of restarts have failed.
If a stop signal is given, the auto-restart sequence is
aborted and the fault
7
Automatic restart
is configured with the following
parameters:
Parameter
09.01
Auto-reset delay time
09.02
Auto-restart
09.03
Auto-restart max attempts
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
relay is not activated.
Description
Delay time after which the event is reset.
Enable auto-restart function.
Max number of auto-restart attempts.
Setting range
Default value
0 ... 3600 s
0 s
Off,On
Off
1 ... 10
5