7.3
Full voltage start
When using the full voltage start the softstarter shall
ensure that the motor accelerates up to full speed as fast
as possible. This is done by providing a full voltage start
in which the motor voltage ramps up to full voltage in ½
seconds.
INFORMATION
Current limit is ignored for full voltage start.
Full voltage start is configured with the following
parameters:
Parameter
02.01 Start mode
7.4
Direct stop
When using the Direct stop the output voltage to the
motor is 0.
7
Direct stop is configured with the following
parameters:
Parameter
02.02 Stop mode
7.5
Stand still brake
The Stand still brake breakes the output to the motor,
and can be used during pre-start to assure that the
motor is standing still before Start ramp is initiated. Stand
still brake can also be controlled from a digital I/O or a
fieldbus.
Stand still brake
is configured with the following
parameters:
Parameter
02.07 Pre-start function
02.08 Pre-start time
07.01 Stand still brake strength
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Set to Full voltage start.
Description
Set to No ramp.
Description
Set to Stand still brake.
Set the duration of the pre-start function.
Set the Braking strength 10-100%. Choose a
suitable value for the application.
Setting range
Default value
Voltage ramp,
Voltage ramp
Torque ramp,
Full voltage ramp
Setting range
Default value
No ramp,
Voltage ramp
Voltage stop
ramp, Torque
stop ramp
Setting range
Default value
Off, Motor
Off
heating, Stand
still brake, Jog
forward, Jog
backward
0.0 ... 7200.0 s
10.0 s
10 ... 100%
50%