Motor Current Ie
Set the motor current before the softstarter is used for the
first time.
The setting of this parameter shall be configured to the
rated nominell current of the motor.
WARNING
All PSTX softstarters must be configured to
the rated current of the motor.
Motor Current Ie is configured with the following
parameters:
Parameter
01.01 Motor Current Ie
* Depends on softstarter model.
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Set the nominal current of the motor. For good performance it
is important that it is set to the correct value. For Inside Delta
connection, this parameter shall be set to 58% of the nominal
motor current.
Setting range
Default value
9.0 A...1250A
*9.0 A