High current fault
7.17.2.4
A fault signal will be given if the motor current exceeds the
fixed set level which is 8*Ir for the duration of the fixed set
time which is 200 ms.
Check the circuits including the motor for any insulation
fault phase to phase or earth fault.
High current fault is configured with the following
parameters:
Parameter
26.07 High current out
26.08 High current op
Faulty usage fault
7.17.2.5
Faulty usage fault is activated if the user tries to use
motor heating and slow speed functions and the motor is
connected inside delta.
Faulty usage fault is configured with the following
parameters:
Parameter
26.09 Faulty usage out
26.10 Faulty usage op
Connection fault
7.17.2.6
Connection fault signals a fault when a fault connection is
detected for both type of connections, in line and inside
delta
Connection fault is configured with the following
parameters:
Parameter
26.11 Faulty connection out
26.12 Faulty connecion op
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Specifies the Event groups this
fault belongs to.
Sets the operation of this fault.
Description
Specifies the Event groups this
fault belongs to.
Sets the operation of this fault.
Description
Specifies the Event groups
this fault belongs to.
Sets the operation of this
fault.
Setting range
Default value
Eventgroup 0 ... 6
1
Stop manual, Stop
Stop manaul
auto
Setting range
Default value
Eventgroup 0 ... 6
1
Stop manual, Stop
Stop manaul
auto
Setting range
Default value
Eventgroup 0 ... 6
1
Stop manual, Stop
Stop manaul
auto