7.15.4
Current underload protection
The motor current has fallen below the settable value.
The voltage to the softstarter is too low. The protection
measures voltage and checks if the voltage is too low, if it
is too low, the softstarter will trip.
This protection is only operational in the Top of ramp
state.
Check that the motor current parameter (Ie) is set
correctly.
Current underload protection is configured with the
following parameters:
Parameter
14.01 Curr underload level
14.02 Curr underload trip time
14.03 Curr underload delay time
14.04 Curr underload out
14.05 Curr underload op
7
7.15.5
Power factor underload protection
The power factor has fallen below the normal level.
The Power factor underload protection can be used to
supervise the load of the motor. If the load decreases the
power factor will decrease as well.
This protection is only operational in the Top of ramp
state.
Power factor underload protection is configured with
the following parameters:
Parameter
14.06 Pwr factor underload level
14.07 Pwr factor underload trip time
14.08 Pwr factor underload delay time
14.09 Pwr factor underload out
14.10 Pwr factor underload op
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Sets the Current underload trip
level.
Sets the time that the current
has to be below the trip level to
trip.
Sets the time after Top of ramp
that the protection is enabled.
Specifies the Event groups this
protection belongs to.
Sets the operation of this
protection.
Description
Sets the Power factor
underload trip level.
Sets the time that the Power
factor has to be below the
trip level to trip.
Sets the time after Top of
ramp that the protection is
enabled.
Specifies the Event groups
this protection belongs to.
Sets the operation of this
protection.
Setting range
Default value
0.3 ... 0.9 x I e
0.3 x I e

0 ... 10 s

1 s
0 ... 30 s
10 s
Eventgroup 0 ... 6
2
Off, Stop manual,
Off
Stop auto, Indication
Setting range
Default value
0.0 ... 1.0
0.7
0 ... 10 s
1 s
0 ... 30 s
10 s
Eventgroup 0 ... 6
2
Off, Stop manual,
Off
Stop auto, Indication.