Siemens 6DR50 Series Operating Instructions Manual page 126

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Commissioning
7.5 Commissioning linear actuators
Setting the actuator
1. Check whether the mechanical unit can be moved freely in the entire travel range. Move
the actuator to the respective end position for this purpose using the
Note
End position
By simultaneously pressing the
2. Now move the actuator to the horizontal position of the lever.
3. A value between "P48.0" and "P52.0" is shown on the display.
4. If a value beyond this value range is shown on the display, you must move the friction
clutch. Move the friction clutch until a value between "P48.0" and "P52.0" is achieved.
The closer this value is to "P50.0", the more accurately the positioner determines the
stroke travel.
Note
The following is applicable for the flameproof enclosure version:
The inner friction clutch is fixed. Therefore, only move the outer friction clutch.
See also
Mounting the linear actuator (Page 34)
Installing the optional modules in the "flameproof enclosure" version (Page 52)
External position detection (Page 48)
124
and
buttons, you reach the end position faster.
Operating Instructions, 09/2014, A5E00074631-12
or
button.