Mechanical Limit Switch Module - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Installing/mounting
4.7 Installing option modules
4.7.5

Mechanical limit switch module

Requirements
You are familiar with the procedure described in the section "Installing optional modules in
the standard and intrinsically safe version (Page 49)".
Procedure for installing the mechanical limit switch module
Figure 4-15
1. Disconnect all electrical connections of the basic electronics.
2. Loosen the two fixing screws of the basic electronics.
3. Remove the basic electronics.
4. Insert the mechanical limit switch module from the top up to the upper printed circuit
board guide of the module rack.
5. Slide the mechanical limit switch module in the printed circuit board of the module rack
approximately 3 mm towards right.
62
Actuating disk bearings
Special screw
Pin
Mechanical limit switch module
Upper actuating disk for limit L1, terminals 41/42
Lower actuating disk for limit L2, terminals 51/52
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12