Procedure for "Manual" mode (MAN)
1. Move the actuator to the desired position of the upper endstop
or lower endstop using the
2. Switch to "Diagnostics" mode.
3. Go to diagnostics parameter 21.P0 (22.P100).
4. Apply the setting by pressing the
seconds. After 5 seconds, "0.0" (with 22.P100: "100.0") is
displayed. Result: The lower endstop (upper endstop) now
corresponds to the current position of the actuator.
5. Switch to "Manual" mode (MAN). Result: Values for the upper
endstop (lower endstop) have changed.
Procedure for "Automatic" mode (AUT)
1. Check in the display whether the current position of the actuator
is at the desired position of the lower endstop (upper endstop).
2. Switch to "Diagnostics" mode.
3. Go to diagnostics parameter 21.P0 (22.P100).
4. Apply the setting by pressing the
seconds. After 5 seconds, "0.0" (with 22.P100: "100.0") is
displayed. Result: The lower endstop (upper endstop) now
corresponds to the current position of the actuator.
5. Switch to "Automatic" mode (AUT).