Alarm, error, and system messages
10.1
Output of system messages in the display
10.1.1
System messages before initialization
Remarks about the tables:
nn
/
Messages before initialization (first commissioning)
Message
Line
Up
Down
CPU
X
Start
X
Pnnn.n
X
P---
X
NOINI
X
See also
Display (Page 103)
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Stands for variable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Meaning / cause
Message after application of electrical auxil-
iary power
Potentiometer voltage of a non-initialized
positioner (P-manual mode) (actual position
value in % of the measuring range).
Measuring range was exceeded, the potenti-
ometer is in the inactive zone, the transmis-
sion ratio selector or the effective lever arm
are not adjusted as per the actuator travel.
Positioner is not initialized.
Measure
Maintenance
•
Check whether the complete travel can
•
be covered using the
and that "P---" is never displayed.
Execute the initialization process.
•
Switch the transmission ratio selector to
•
90°, especially in the case of part-turn ac-
tuators.
Adjust the effective lever length of linear
•
actuators as per the measuring range.
Start initialization.
•
10
and
buttons