Siemens 6DR50 Series Operating Instructions Manual page 203

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Messages during initialization
Message
Line
Up
Down
P--
X
RUN1
X
RUN2
X
RUN3
X
RUN4
X
RUN5
X
YEND1
X
YEND2
X
RANGE
X
ok
x
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Meaning / cause
Measuring range was exceeded, the potenti-
ometer is in the inactive zone, the transmis-
sion ratio selectors or the effective lever arm
are not adjusted as per the actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of end stops)
Initialization part 3 is active (determination
and display of travel times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first end position can be approached
only in case of a manual initialization
The second end position can be approached
only in case of a manual initialization
The end position or the measuring span is
beyond the permissible measuring range
only in case of a manual initialization
The permissible measuring range of end
positions is achieved only in case of a man-
ual initialization
Alarm, error, and system messages
10.1 Output of system messages in the display
Measure
Switch the transmission ratio selector to
90° especially in case of part-turn actua-
tors
Adjust the effective lever length of linear
actuators as per the measuring range
Maintenance
Maintenance
Maintenance
Maintenance
Wait until "FINSH" is displayed (initializa-
tion completed successfully)
Acknowledge by pressing the operating
mode button briefly and exit the configu-
ration level by pressing it longer
Approach the first end position using the
"+" or "-" button
Acknowledge using the operating mode
button
Approach the second end position using
the "+" or "-" button
Acknowledge using the operating mode
button
Approach another end position using the
"+" and "-" buttons and acknowledge with
the operating mode button, or
Move the friction clutch until "ok" is dis-
played, and then acknowledge with the
operating mode button, or
Terminate the initialization process by
pressing the operating mode button,
switch to the P-manual mode and correct
the actuator travel and the position dis-
placement sensor
Acknowledge with the operating mode
button; the remaining steps ("RUN1" to
"FINSH") execute automatically
201