Siemens 6DR50 Series Operating Instructions Manual page 204

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.1 Output of system messages in the display
Message
Line
Up
Down
RUN1 /
X
ERROR
X
d___U
SEt
X
MIDDL
X
X
UP >
X
90_95
X
U-d>
U nn.n
X
D->U
X
D nn.n
X
U->d
X
202
Meaning / cause
Error in "RUN1", no movement e.g. due to
the lack of compressed air
Bar graph display of the zero point; zero
point is beyond the tolerance range
Friction clutch was moved; "P 50.0" not dis-
played when the lever is horizontal
"UP" tolerance range was exceeded or the
inactive zone of the potentiometer was cov-
ered
Possible only in case of part-turn actuators:
actuator travel is not in the range between 90
and 95%
"Up-Down" measuring span was undershot
Display of the "Up" travel time
Display of the "Down" travel time
Measure
Provide adequate compressed air
Open the restrictor(s)
Restart the initialization process
Set between "P 4.0" and "P 9.9" ( >0< )
using a friction clutch
Continue with the "+" or "-" button
In case of linear actuators, use the "+"
and "-" buttons to bring the lever perpen-
dicular to the spindle
Press the operating mode button slightly
to acknowledge (the initialization process
is continued)
Increase the effective lever length of the
linear actuators or switch the transmis-
sion ratio selector to 90°
Press the operating mode button slightly
to acknowledge
Restart the initialization process
Use the "+" and "-" buttons to move it in
the range between 90 and 95%
Press the operating mode button slightly
to acknowledge
Decrease the effective lever length of the
linear actuators or switch the transmis-
sion ratio selector to 33°
Press the operating mode button slightly
to acknowledge
Restart the initialization process
Wait, or
To change the travel time, interrupt the
initialization process with the "-" button,
or
Activate the leakage test with the "+"
button
Wait, or
To change the travel time, interrupt the
initialization process with the "-" button,
or
Activate the leakage test with the "+"
button
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12