Alarm, error, and system messages
10.2 Diagnostics
10.2.3.10

Diagnostics parameter '12.PST' Monitoring of partial stroke test

Indication on the display: • OFF
Purpose:
Description of indications
on the display:
Status messages:
Factory setting:
10.2.3.11

Diagnostics parameter '13.PRPST' Time since last partial stroke test

Indication on the display: • ###
Purpose:
212
• FdInI
• notSt
• ###.#
• SdtSt
• FdtSt
This diagnostics parameter indicates the stroke time measured
during the last partial stroke test.
A partial stroke test can be initiated manually or a current partial
stroke test can be interrupted by pressing the
• OFF: The partial stroke test function is deactivated in the
configuration menu.
• FdIni - Failed PST Initialization: The reference stroke time
measurement of the partial stroke test has failed.
• notSt - No Test: A partial stroke test has not yet been executed.
• ###.#: Corresponds to the measured stroke time in seconds.
The last partial stroke test was successfully executed.
• SdtSt - Stopped Test: The last partial stroke test was
interrupted.
FdtSt - Failed Test: The last partial stroke test has failed.
The following status messages appear when you hold the
ton pressed:
• notoL - No Tolerance: The control valve is beyond the tolerance
range to start the partial stroke test. A manual partial stroke test
is not started.
• Strt - Start: A manual partial stroke test is started after pressing
the button for five seconds.
• StoP - Stop: The currently running partial stroke test is
interrupted.
OFF
• notSt
• Sdtst
• fdtSt
This diagnostics parameter shows the elapsed time in days since
the last partial stroke test.