Yway' Range Of Stroke; Inita' Initialization (Automatically) - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Parameterizing/addressing
9.4 Description of parameters
See also
Sequence of automatic initialization (Page 117)
9.4.1.3

'3.YWAY' Range of stroke

Requirement:
Possible settings:
Purpose:
Factory setting:
9.4.1.4

'4.INITA' Initialization (automatically)

Possible settings:
Purpose:
Factory setting:
158
• Positioner is mounted.
• Carrier pin is mounted on the lever in accordance with the
actuator's range of stroke as described in section "Mounting the
linear actuator (Page 34)", "Figure 4-2 Lever with carrier pin
(Page 37)".
• OFF
• 5.0 | 10.0 | 15.0 | 20.0 | 25.0 |30.0 | 35.0 | 40.0 |
50.0 | 60.0 | 70.0 | 90.0 | 110.0 | 130.0
Use this parameter to display the determined stroke value in mm
when initialization of a linear actuator has been completed.
If you select the "OFF" setting, the real stroke is not displayed after
initialization.
From the possible settings shown above, select the value which
corresponds to the range of stroke of your actuator in mm.
If the range of stroke of the actuator does not correspond to a pos-
sible setting, use the next higher value. Use the value specified on
the nameplate of the actuator for this purpose.
OFF
• NOINI
• no / ###.#
• Strt
Use this parameter to start the automatic initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
The sequence of the initialization process from "RUN1" to "RUN5"
is output in the bottom line of the display.
NOINI
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12