Parameterizing/addressing
9.3 Parameter overview
Overview parameter F
Parameter
Function
Monitoring of lower endstop with the following parameters:
F. ZERO
F1.LEVL1
Threshold 1
F2.LEVL2
Threshold 2
F3.LEVL3
Threshold 3
Overview parameter G
Parameter
Function
Monitoring of upper endstop with the following parameters:
G. OPEN
G1.LEVL1
Threshold 1
G2.LEVL2
Threshold 2
G3.LEVL3
Threshold 3
Overview parameter H
Parameter
Function
Monitoring of lower limit temperature with the following parameters:
H. TMIN
H1.TUNIT
Temperature unit
H2.LEVL1
Threshold 1
H3.LEVL2
Threshold 2
H4.LEVL3
Threshold 3
Overview parameter J
Parameter
Function
Monitoring of upper limit temperature with the following parameters:
J. TMAX
J1.TUNIT
Temperature unit
J2.LEVL1
Threshold 1
J3.LEVL2
Threshold 2
J4.LEVL3
Threshold 3
154
Parameter values
0.1 ... 1.0 ... 10.0
0.1 ... 2.0 ... 10.0
0.1 ... 4.0 ... 10.0
Parameter values
0.1 ... 1.0 ... 10.0
0.1 ... 2.0 ... 10.0
0.1 ... 4.0 ... 10.0
Parameter values
°C
°F
-40 ... -25 ... 90
-40 ... 194
-40 ... -30 ... 90
-40 ... 194
-40 ... 90
-40 ... 194
Parameter values
°C
°F
-40 ... 75 ... 90
-40 ... 194
-40 ... 80 ... 90
-40 ... 194
-40 ... 90
-40 ... 194
Operating Instructions, 09/2014, A5E00074631-12
Unit
%
Unit
%
Unit
°C/°F
Unit
°C/°F
SIPART PS2 with and without HART