Commissioning
7.5 Commissioning linear actuators
Initializing the linear actuator automatically
1. Switch to the "Configuration" mode. To do this, press the
until the display shows the following:
2. Call the "2.YAGL" parameter. To do this, briefly press the
shown on the display depending on the setting:
3. Check whether the value displayed of the "2.YAGL" parameter matches with the setting
of the transmission ratio selector. If required, change the setting of the transmission ratio
selector to 33° or 90°.
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of the
"3.YWAY" parameter is optional. The display shows the determined total stroke only at
the end of the initialization phase.
– Briefly press the
– Call the "3.YWAY" parameter. To do this, briefly press the
Note
Set the "3.YWAY" parameter
To set the "3.YWAY" parameter proceed as follows:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter to the read value with the
128
button if you do not require any information about the total stroke
in mm. You are then directed to parameter 4.
shows the following:
button for at least 5 seconds
button. The following is
button. The display
or
button.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12