Siemens 6DR50 Series Operating Instructions Manual page 209

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

No.
Abbreviation
Meaning
11
LEAK
Leakage
12
PST
Partial stroke tests
13
PRPST
Time since the last partial stroke test
14
NXPST
Time until the next partial stroke test
15
DEVI
Dynamic control valve behavior
16
ONLK
Pneumatic leakage
17
STIC
Stiction (slipstick)
18
ZERO
Lower endstop
19
OPEN
Upper endstop
20
PAVG
Average value of position
21
P0
Potentiometer value of lower endstop (0%)
22
P100
Potentiometer value of upper endstop (100%)
23
IMPUP
Impulse length up
24
IMPDN
Impulse length down
25
PAUTP
Pulse interval
26
DBUP
Deadband up
27
DBDN
Deadband down
28
SSUP
Slow step zone up
29
SSDN
Slow step zone down
30
TEMP
Current temperature
31
TMIN
Minimum temperature ("min/max pointer")
32
TMAX
Maximum temperature ("min/max pointer")
33
T1
Number of operating hours in temperature range 1
34
T2
Number of operating hours in temperature range 2
35
T3
Number of operating hours in temperature range 3
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Alarm, error, and system messages
Representable
Unit
diagnostics val-
ues
- / 0.0 ... 100.0
%/minute
OFF / ###.#, fdini,
s for ###.#
notSt, SdtSt,
fdtSt, notd, Strt,
StoP
###, notSt, Sdtst,
Days
fdtSt
OFF / ###
Days
OFF / 0.0 ...
%
100.0
OFF / 0.0 ...
-
100.0
OFF / 0.0 ...
%
100.0
OFF / 0.0 .. 100.0 %
OFF / 0.0 ...
%
100.0
OFF, IdLE, rEF,
%
COMP
0.0 ... 100.0
0.0 ... 100.0
%
0.0 ... 100.0
%
6 ... 160
ms
6 ... 160
ms
2 ... 28 ... 320
ms
0.1 ... 10.0
%
0.1 ... 10.0
%
0.1 ... 10.0 ...
%
100.0
0.1 ... 10.0 ...
%
100.0
-50 ... 100
° C
-58 ... 212
° F
-50 ... 100
° C
-58 ... 212
° F
-50 ... 100
° C
-58 ... 212
° F
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
10.2 Diagnostics
Properties
207