Advertisement

4.7.4

Slot initiator alarm module

Function
If the standard controller requires electrically independent limit value messages, the slotted
initiator alarm module with slotted initiators is used instead of the alarm module.
● A binary output is used to display a collective fault message. Compare with the function of
the alarm module. The floating binary output is implemented as an automatic fault
indicating semiconductor output.
● The other two binary outputs are used to signal the two limits L1 and L2 which can be
adjusted mechanically using slotted initiators. Both these binary outputs are electrically
independent from the remaining electronic unit.
Device features
Figure 4-14
The slotted initiator alarm module, SIA module for short, consists of three binary outputs
Requirements
You are familiar with the general procedure described in the section "Installing optional
modules in the standard and intrinsically safe version (Page 49)".
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Actuating disk bearings
Special screw
Pin
SIA module
Upper actuating disk for limit L1, terminals 41/42
Lower actuating disk for limit L2, terminals 51/52
Binary outputs
Installing/mounting
4.7 Installing option modules
.
59