7.17.18 Too long start time protection
Too long start time protection
Too long start time protection has these parameters:
Parameter
18.11 Too long start trip time
18.12 Too long start out
18.13 Too long start op
7.17.19 Auto restart protection
Auto restart protection
Auto restart protection has these parameters:
Parameter
18.14 Auto restart max delay
18.15 Auto restart time-out out
1816 Auto restart time-out op
7
7.17.20 HMI failure protection
This protection senses errors in communication between
the Softstarter and the HMI, while the Softstarter is in
local control.
If the communication with the HMI is lost for more than
approximately 600 ms this protection is on.
This protection has a special action in addition to the
common types of operation:
Stop HMI control - stop the local control and change to
remote control i.e digital input or Fieldbus.
HMI failure protection has these parameters:
Parameter
19.01 HMI failure out
19.02 HMI failure op
110
Functions | Installation and commissioning manual |
Description
Trip time in seconds.
Specifies the Event groups this
protection belongs to.
Sets the operation of this
protection.
Description
Max restart time in seconds
Specifies the Event groups this
protection belongs to.
Sets the operation of this
protection.
Description
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
1SFC132081M0201
Setting range
Default value
1.0 ... 500.0 s
500.0 s
Eventgroup 0 ... 6
0000010
Off, Stop-Manual,
Off
Stop-Automatic,
Indication, Fast ramp
Setting range
Default value
2 ... 3600 s
3600 s
Eventgroup 0 ... 6
0000010
Off, Stop-Manual,
Off
Stop-Automatic,
Indication
Setting range
Default value
Eventgroup 0 ... 6
0000010
Off, Stop-Manual,
Stop-Manual
Stop-Automatic,
Indication, Stop HMI
control