Configuration
For a quick configuration of the Softstarter, use the
Assistants menu.
The Assistants menus are divided into:
Basic set-up
- The Basic set-up menu is divided into 4 steps:
1. Language
2. Date and time
3. Motor data
4. System configuration
Application set-up
2
- The Application set-up is divided into 3 steps:
1. Application set-up
2. Keep/Change values
3. Tune settings
2.2.1
Basic set-up
You see this set-up when you start the Softstarter. To
disable this set-up, see step 6 below.
1.
Find the Assistants menu by pushing
Scroll to Assistants with the Navigation keys. Push
"Select" to enter the Assistants menu.
2.
Scroll to the Basic set-up menu with the
Navigation keys. Push
menu.
3.
The Basic set-up starts with step 1 of 5,
Language. Push
Use the Navigation keys to select language and
then push
4.
Push
to enter step 2(5), Date and time. Push
"Edit" and use the Navigation keys to edit date
and time, then push
5.
Push
to enter step 3(5), Motor data.
Push
"Edit" to change the Motor rated current
Ie. Use the Navigation keys to change the value
and then push
6.
Push
to enter step 4(5), System configuration.
Here you can set if the Softstarter enters the Basic
set-up at power on or not. Use the Navigation keys
to select Yes or No and then push
7.
Push
to enter step 5(5) and then Push
"Done" to finish the Basic setup. For more
settings, enter Application set-up.
14
Quick start | Installation and commissioning manual |
"Menu".
"Select" to enter the
"Edit" to change language.
"Save".
"Save".
"Save".
"Save".
2.2.2
Application set-up
1.
Find the Assistants menu from the Home view by
pushing
"Menu". Scroll to Assistants with the
Navigation keys. Push
Assistants menu.
2.
Scroll to the Application set-up menu with the
Navigation keys and then enter the menu by
pushing
"Select".
3.
The Application set-up will start with step 1,
Application type. Scroll to the appropriate
application type and then push
a full Application list, see
parameter
list.
4.
Push
to enter step 2, Values. You can select
"Keep actual values" or "Change to recommended
values". Scroll to the selection of your choice and
Push
"Select" to apply.
WARNING!
Note that your saved parameter values are lost if you
select "Change to recommended values".
5.
Push
to enter step 3, Tune settings. In most
cases the recommended values are sufficient, but
sometimes fine tuning is necessary. For fine tuning,
push
"Edit" and then use the navigation keys
to set:
-Start ramp time: 1 - 120s
-Stop ramp time: 1 - 120s
-Start ramp initial level: 10 - 99%
-Stop ramp end level: 10 - 99%
-Current limit level: 1.5 - 7.5 x Ie
-Start mode: Voltage ramp, Torque ramp or Full
voltage start
-Stop mode: No ramp, Voltage ramp, Torque ramp,
Dynamic brake
6.
Push
and then push
Application set-up. If necessary, fine tuning can
also be done in the Parameters menu.
1SFC132081M0201
"Select" to enter the
"Select". For
chapter
7.25 Complete
"Done" to finish the