7.6
Stand still brake
The Stand-still brake function brakes the motor. Use this
during pre-start to make sure that the motor does not run
before you start the Start ramp. You can also control the
Stand-still brake from a digital I/O or a Fieldbus.
WARNING
If the Softstarter is connected inside-delta,
use of the Stand-still brake can cause
damage to the equipment.
WARNING
Because this function makes the motor
warm, we recommend to use a PTC or
PT100 element to monitor the temperature.
In some conditions, the built-in EOL is not
accurate for this feature.
INFORMATION
Stand-still brake only works when the Softstarter
is connected in-line.
Configuration of the Stand-still brake with these
parameters:
7
Parameter
02.07 Pre-start function
02.08 Pre-start time
07.01 Stand still brake strength
82
Functions | Installation and commissioning manual |
Description
Set to Stand-still brake.
Set the duration of the pre-start function.
Set the Braking strength 10-100%. Select a suitable
value for the application.
1SFC132081M0201
Setting range
Default value
Off, Motor
Off
heating, Stand-
still brake, Jog
forward, Jog
backward
0.0 ... 7200.0 s
10.0 s
10 ... 100%
50%