7.14.4
Analog output
The Softstarter has 1 analog output for an analog meter,
or the PLC.
Configuration of the parameter analog output type, AO
type, to show:
Motor current, A
Mains voltage, V
Active power, kW
Active power, HP
Reactive power, kVar
Apparent power, kVA
Active energy, kWh
Reactive energy, kVArh
cos phi
Motor temperature, %
Thyristor temperature, %
Motor voltage, %
Mains frequency, Hz
PT100 temperature, centigrade
PTC resistance, Ohm
The voltage or current output can be set by a
configuration parameter, AO reference in the Softstarter.
The selection of voltage or current must be set to adapt
to the analog meter or the PLC.
The settings are:
0-10 voltage output, V
0-10 current output, mA
0-20 current output, mA
4-20 current output, mA
AO is the reference to the output voltage in 0-100% of
the set parameter AO max and AO min.
Internal Analog output has these parameters:
Parameter
Description
10.07 AO reference
Sets the Analog output reference
10.08 AO type
Sets the Analog output type.
10.09 AO max value
Sets the max analog output
value.
10.10 AO min value
Sets the min analog output value.
External Analog output (Extension I/O) has these
parameters:
Description
Description
11.13 1AO0 reference
Sets the Analog output
reference.
11.14 1AO0 type
Sets the Analog output type.
11.15 1AO0 max value
Sets the max Analog output
value.
11.16 1AO0 min value
Sets the min Analog output
value.
Example:
AO type is set to Motor current.
AO reference is set to 0-10 V
AO min to 0, and AO max to 3000.
This means that when the motor current is:
3000 A, the output voltage is 10 V.
0 A, the output voltage is 0 V.
1500 A, the output voltage is 5 V.
Setting range
0-10 mA, 0-20 mA, 4-20 mA, 0-10 V
Motor current, Mains voltage, Active power,
Active power, Reactive power, Apparent power,
Active energy,Reactive energy, cos fi, Motor
temperature, Thyristor temperature, Motor
voltage, Mains frequency, PT100 temperature,
PTC resistance
0,0 ... 1000000
0,0 ... 1000000
Setting range
0-10 mA, 0-20 mA, 4-20 mA, 0-10 V
Motor current, Mains voltage, Active power, Active
power, Reactive power, Apparent power, Active
energy,Reactive energy, cos fi, Motor temperature,
Thyristor temperature, Motor voltage, Mains
frequency, PT100 temperature, PTC resistance
0,0 ... 1000000
0,0 ... 1000000
1SFC132081M0201
| Installation and commissioning manual | Functions
7
Default value
4-20 mA
Motor current, A
500
0
Default value
4-20 mA
Motor current, A
500
0
95