ABB PSTX Series Installation And Commissioning Manual page 45

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

Programmable output relay - K4,
5.1.2.6
terminals 4, 5 and 6
See chapter 7.14 Inputs/outputs to set the function of
the output relay.
Default: Run
Connect the cables to terminal 4, 5 and 6.
See Figure 5.17.
Recommended to control line contactor.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Programmable output relay - K5,
5.1.2.7
terminals 7, 8 and 9
See
chapter
7.14 Inputs/outputs to set the function of
the output relay.
Default: Top of ramp
Connect the cables to terminal 7, 8 and 9.
See Figure 5.18.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Programmable output relay - K6,
5.1.2.8
terminals 10, 11 and 12
See
chapter
7.14 Inputs/outputs to set the function of
the output relay.
Default: Event
Connect the cables to terminal 10, 11 and 12.
See Figure 5.19.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Start Stop In0 In1 In2
GND
+24V
K6
Start Stop In0 In1 In2
GND
+24V
K6
K6
Start Stop In0 In1 In2
GND +24V
1SFC132081M0201
Figure 5.17
Programmable output relay K4, terminals 4, 5 and 6
M3,5
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
Figure 5.18
Programmable output relay K5, terminals 7, 8 and 9
M3,5
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
Figure 5.19
Programmable output relay K6, terminals 10, 11 and 12
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
| Installation and commissioning manual | Connection
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
5
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
45