ABB PSTX Series Installation And Commissioning Manual page 116

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

7.18.12 Short circuit warning
There is an internal short circuit and limp mode is
enabled. If limp mode is off, this is a short circuit fault
instead.
Speak to ABB Sales Offices for service.
Short circuit warning has these parameters:
Parameter
23.07 Short circuit out
23.08 Short circuit
7.18.13 Number of starts warning
Number of starts warning
Number of starts warning has these parameters:
Parameter
24.01 Number of starts limit
24.02 Number of starts out
24.03 Number of starts
7
7.18.14 Modbus configuration warning
The built-in modbus RTU slave is enabled (parameter
12.02) but the Com3 function is not set to modbus RTU
slave. To use modbus RTU, enable the RTU slave and set
the modbus RTU slave to use the Com3 port.
Modbus configuration warning has these parameters:
Parameter
24.06 Modbus_RTU w/o auxport out
7.18.15 Phase loss warning
Phase loss warning.
Phase loss warning has these parameters:
Parameter
24.07 Phase loss trip time
24.08 Phase loss out
24.09 Phase loss
116
Functions | Installation and commissioning manual |
Description
Identifies the Event groups this warning is
part of.
Enables Short circuit warning.
Description
Max number of starts
Specifies the Event groups this warning
belongs to.
Enables Number of starts warning
Description
Identifies the Event groups this
warning belong to.
Description
Trip time in seconds
Specifies the Event groups this
warning belongs to.
Enables Phase loss warning
1SFC132081M0201
Setting range
Default value
Eventgroup 0 ... 6
0000100
Off, On
On
Setting range
Default value
1 ... 65535
65535
Eventgroup 0 ... 6
0000100
Off, On
Off
Setting range
Default value
Eventgroup 0 ... 6
0000100
Setting range
Default value
0.5 ... 100.0 s
3.0 s
Eventgroup 0 ... 6
0000100
Off, On
Off