ABB PSTX Series Installation And Commissioning Manual page 41

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

Start and Stop - terminals 13, 14, 18, 19,
5.1.2.3
20, 21
Internal control voltage
The PSTX Softstarter has a built-in holding circuit and
does not require sustained signals on start input. Use
internal control supply voltage from terminals 20 or 21.
Connect start and stop terminals using conventional
circuit with push buttons. See Figure 5.6 and Figure 5.7.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
A conventional circuit with auxiliary relay is also possible.
See Figure 5.8.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
K6
Start
Stop In0 In1 In2
GND
+24V
K6
Start Stop In0 In1 In2
GND
+24V
K6
Start Stop In0 In1 In2
GND
+24V
1SFC132081M0201
Figure 5.6
Start and Stop, terminals 13, 14, 18, 19, 20, 21
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
STOP
L
N
100-250V
50/60 Hz
K4
K5
Figure 5.7
Holding circuit (pulse for start is enough)
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
L
N
100-250V
50/60 Hz
K4
K5
Figure 5.8
Conventional circuit (maintained start signal required)
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
| Installation and commissioning manual | Connection
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
START
K6
Start Stop In0 In1 In2 DGND GND +24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
L
STOP
START
N
SPARE
K6
Start Stop
In0
In1 In2 DGND GND +24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
41
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents