FusionModule1000A20 IT Solution
Installation Guide (2016.05, AI Version)
Skill requirement: skilled technician, common technician
Procedure
Step 1 Determine the dehumidifier installation position based on the cooling device layout diagram.
Step 2 Secure the lugs of the dehumidifier on both sides of the chassis, and place the dehumidifier on
the bottom tray in the cabinet. Then secure the dehumidifier lugs to the cabinet rack rail.
Figure 9-17 Installing a dehumidifier
Step 3 Determine the position of the pagoda connector port reserved for the dehumidifier on the
drainpipe under the raised floor by referring to the cooling device layout diagram.
Step 4 Remove the raised floor, clip the dehumidifier drainpipe to the pagoda connector reserved
under the floor using a Phillips screwdriver and a hoop, and open the ball valve connected to
the pagoda connector.
Step 5 After connecting pipes, reinstall the raised floor.
Step 6 Connect one end of the adapter delivered with the dehumidifier to the dehumidifier power
cable, and connect the other end to the circuit breaker reserved for the dehumidifier in the
PDC.
----End
Follow-up Procedure
Verify that the dehumidifier is reliably installed.
Issue 02 (2017-01-10)
For the diagram, see the quick installation guide for the solution in use.