ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
Fuses
Note: The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other fuse manufacturers can be used if they meet the
specifications given in the table.
• Fuses with higher current rating than specified must not be used.
480 Volt fuses
ACH580-3PxR-07A6-4
ACH580-3PxR-012A-4
ACH580-3PxR-014A-4
ACH580-3PxR-023A-4
ACH580-3PxR-027A-4
ACH580-3PxR-034A-4
ACH580-3PxR-044A-4
ACH580-3PxR-052A-4
ACH580-3PxR-065A-4
ACH580-3PxR-077A-4
1) "PxR" represents both PCR and PDR.
Nominal Output
Ratings
Type Code
Drive
Current
A
7.6A
12A
14A
23A
27A
34A
44A
52A
65A
77A
Internal Drive Fuse Rating
Base
Drive
Package
Frame
Power
Class
Size
HP
480 Volts
5
R3
Class CC
7.5
R3
Class CC
10
R3
Class CC
15
R3
Class CC
20
R6
Class T
25
R6
Class T
30
R6
Class T
40
R6
Class T
50
R6
Class T
60
R6
Class T
123
Max Current
Rating
15A
15A
30A
30A
40A
60A
60A
80A
90A
100A
ACH580-3PCR/3PDR