ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
R8
Analog and
Digital Inputs
Power wiring torque table
Frame size
T1/U, T2/V, T3/W
L1, L2, L3
UDC+ and UDC-
PE Ground
Control terminals
Power terminals
R8
lb-ft
N•m
29.6
29.6
29.5
7.2
40
40
40
9.8
ACH580 Ultra-Low Harmonic Drives Installation
29
Route cables using the
provided tie-downs
Motor leads
Grounding