Download Print this page

ABB ACH580 Series Installation, Operation And Maintenance Manual page 92

Ultra-low harmonic drives
Hide thumbs Also See for ACH580 Series:

Advertisement

92
Standard enclosure terminals maximum wire size and terminal torque values
ACH580-3BCR/BDR
ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
1, 3
Type Code
ACH580-3BxR-07A6-4
ACH580-3BxR-012A-4
ACH580-3BxR-014A-4
ACH580-3BxR-023A-4
ACH580-BxR-027A-4
ACH580-BxR-034A-4
ACH580-BxR-044A-4
ACH580-3BxR-052A-4
ACH580-3BxR-065A-4
ACH580-3BxR-077A-4
1)
"BxR" represents both BCR and BDR.
2)
BCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3)
BCR supports Delta network configuration.
4)
BDR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
Nominal Output
Ratings
Base
Drive
Package
Circuit
Drive
Current
Power
Breaker
Frame
UL Type
Size
1 and 12
A
HP
(NEMA
1 and 12)
480 Volts
7.6
5
R3
#12
62 in-lbs
12
7.5
R3
14
10
R3
#10
62 in-lbs
23
15
R3
27
20
R6
34
25
R6
62 in-lbs
44
30
R6
52
40
R6
#2
65
50
R6
62 in-lbs
77
60
R6
Maximum Wire Size and Terminal Torque
Disconnect
Motor
Switch
Terminals
UL Type
UL Type
1 and 12
1 and 2
(NEMA
(NEMA
1 and 12)
1 and 2)
#10
55 in-lbs
#6
#8
11-13 in-lbs
55 in-lbs
#6
55 in-lbs
#4
55 in-lbs
#8
#1
35 in-lbs
#3
55 in-lbs
#2
55 in-lbs
#1
#2/0
55 in-lbs
110 in-lbs
#1/0
75 in-lbs
Ground
Lugs
UL Type
1 and 2
(NEMA
1 and 2
#4
35 in-lbs
#2
50 in-lbs