ABB ACH580 Series Installation, Operation And Maintenance Manual page 71

Ultra-low harmonic drives
Hide thumbs Also See for ACH580 Series:

Advertisement

ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
Code
(hex)
9083
9084
9085
FA81
FA82
FF61
Fault / Aux. code
External fault 3
(Editable message text)
Programmable fault: 31.05
External event 3 source
31.06 External event 3
type
External fault 4
(Editable message text)
Programmable fault: 31.07
External event 4 source
31.08 External event 4
type
External fault 5
(Editable message text)
Programmable fault: 31.09
External event 5 source
31.10 External event 5
type
Safe torque off 1
Safe torque off 2
ID run
0001
Cause
Fault in external device
Check the external device.
3.
Check setting of parameter 31.05
External event 3 source.
Fault in external device
Check the external device.
4.
Check setting of parameter 31.07
External event 4 source.
Fault in external device
Check the external device.
5.
Check setting of parameter 31.09
External event 5 source.
Safe torque off function
Check safety circuit connections. For
is active, ie. STO circuit
more information, see chapter The
1 is broken.
Safe torque off function in the
Hardware manual of the drive and
Safe torque off function
description of parameter 31.22 STO
is active, ie. STO circuit
indication run/stop.
2 is broken.
Check the value of parameter 95.04
Control board supply.
Motor ID run was not
Check the nominal motor values in
completed successfully.
parameter group 99 Motor data.
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
Maximum current limit
Check settings of parameters 99.06
too low.
Motor nominal current and 30.17
Maximum current. Make sure that
30.17 > 99.06.
Check that the drive is dimensioned
correctly according to the motor.
ACH580 Ultra-Low Harmonic Drives Installation
71
What to do