Branch circuit protection
Input power is connected to the ACH580 with E-Clipse Bypass through a door
interlocked disconnect switch or circuit breaker. Neither of these inputs are fused.
The branch circuit that provides power to the ACH580 with E-Clipse Bypass with
disconnect switch must include appropriate motor branch circuit protective devices
to provide short circuit and ground fault protection for the motor in the bypass mode.
When connected to a 480V power source, the ACH580 with E-Clipse Bypass
with the circuit breaker option is suitable for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical amperes.
Fuses
Note: The UL listed drive fuse in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they meet the
specifications given in the table.
• Fuses with higher current rating than specified must not be used.
480 Volt fuses for box
Type Code
ACH580-3BxR-07A6-4
ACH580-3BxR-012A-4
ACH580-3BxR-014A-4
ACH580-3BxR-023A-4
ACH580-3BxR-027A-4
ACH580-3BxR-034A-4
ACH580-3BxR-044A-4
ACH580-3BxR-052A-4
ACH580-3BxR-065A-4
ACH580-3BxR-077A-4
1) "BxR" represents both BCR and BDR.
enclosures
Nominal Output Ratings
Drive
Package
Frame
Current
Power
A
HP
480 Volts
7.6
5
12
7.5
14
10
23
15
27
20
34
25
44
30
52
40
65
50
77
60
Internal Drive
Base
Fuse Rating
Drive
Max
Class
Current
Size
Rating
R3
Class CC
15A
R3
Class CC
15A
R3
Class CC
30A
R3
Class CC
30A
R6
Class T
40A
R6
Class T
60A
R6
Class T
60A
R6
Class T
80A
R6
Class T
90A
R6
Class T
100A
93