(b) Initialization setting
Perform the following operations to configure settings for initialization.
(c) Countermeasures for abnormal completion
Flashing of the ERR. LED indicates abnormal completion.
• If the 7-segment LED shows "Eb" and "EC" an error occurred during the initialization setting.
• If the 7-segment LED is off and only ERR. LED flashed, a system error is present.
When any error has occurred, take initialization steps again. If failure is detected again, any hardware error
may exist. Please consult your local Mitsubishi service center or representative, explaining the details of the
problem.
68
1.
Move the RESET/SELECT switch to the RESET position.
2.
Check that the MODE LED goes off.
3.
Move the RUN/STOP/MODE switch to MODE position.
Do not release the switch while pulling it down.
4.
Move the RESET/SELECT switch back to the center.
5.
Check that the MODE LED turns on in orange.
7-segment LED indicates "00".
6.
Move the RUN/STOP/MODE switch back to the STOP
position.
Release the switch then it returns to its center position.
7.
Move the RESET/SELECT switch to the SELECT position.
Each time you move the switch to the SELECT position, the
mode changes and a value representing the respective mode
is displayed by the LEDs.
Repeat this step until the 7-segment LED shows target mode
in the table below.
Mode
10
Default IP setting
11
Module initialization setting (Basic mode)
12
Module initialization setting (Extended mode)
*1 :
Be sure to select Mode 12 to perform the initialization. If
Mode 11 is selected, the mode becomes the basic mode
and cannot be connected with SW4PVC-CCPU.
8.
Move the RUN/STOP/MODE switch back to RUN position.
During execution of the initialization setting, RUN LED is
flashed green.
9.
Check that the RUN LED goes off.
7-segment LED indicates "00".