The meaning of the status columns is as follows:
AB = Acquisition blocking active (acquisition blocking for the switching device is set)
MU = Manual update (switching device was manually updated)
CH = Chatter blocking active (Chatter blocking has been activated and is still set)
8.9.9

Setting a Marker

In order to be able to set a marker manually with a device operation, you must activate a cross in the Control
Menu column in the DIGSI 5 information matrix (see
[scrangma-090413-01.tif, 1, en_US]
Figure 8-73
The marker appears in a list, for example, under
Commands → Additional → Display or → Status.
At this point you can observe or vary the current status.
NOTE
i
i
To change the state of a marker (from On to Off or vice versa), you need to enter the confirmation ID for
control.

Assignment of Authorizations with Confirmation ID

8.9.10
Sensitive operations during on-site operation are authorized by the assignment of confirmation IDs (see also
Security Manual C53000-H5040-C081).
Figure 8-74
shows an example of a device without a key switch. For devices with key switches, the confirma-
tion IDs are not required for non-interlocked switching and for the switching authority. These are replaced by
the corresponding key switches for non-interlocked control and for local switching authority.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Status Display of Switching Devices
Routing of a Marker to the Operating Menu
Figure
8-73).
Operation in the Operating State
8.9 Control System on Site
209