2.3 Surface-Mounted Devices With Detached On-Site Operation Panel; Basic Rules For Expansion - Siemens SIPROTEC 5 Manual

V8.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

2.3
Surface-Mounted Devices with Detached On-Site Operation Panel

Basic Rules for Expansion

2.3.1
NOTE
i
i
Prepare the following tools for the device expansion:
Phillips screwdriver size PZ1 and PZ2
Screwdriver DIN 4 x 0.8
During assembly, use the prescribed torques
Comply with the following basic rules when expanding devices:
Always fit the base module on the right in the 1st device row.
Always fit the expansion modules from right to left.
Always fit the on-site operation panel of the base module on the left.
Always fit the on-site operation panels of the expansion modules from left to right.
Always install a power-supply module PS203 on the right as the first unit in the 2nd device row.
Note that the PS203 must always have the same rated voltage as the base module.
Always mount the redundant PS204 power-supply module at the position at the very left in the corre-
sponding row (seen from the front). If a CB202 PCB assembly is used in the row, this CB202 PCB assembly
must always be plugged on the left of the power-supply module PS204 (at the very left).
Note that the power-supply module PS204 must always have the same rated voltage as the base module.
The distance between the device and the on-site operation panel is limited to not more than 5 m
(196.85 in) by the length of the connecting cable.
[dwauizei-040211-01.tif, 1, --_--]
Figure 2-4
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Device Row

2.3 Surface-Mounted Devices with Detached On-Site Operation Panel

Expanding Devices
33